1. EXECUTIVE SUMMARY
- CVSS v4 7.1
- ATTENTION: Exploitable remotely/low attack complexity/public exploits are available
- Vendor: Advantech
- Equipment: WebAccess/SCADA
- Vulnerability: SQL Injection
2. RISK EVALUATION
Successful exploitation of this vulnerability could allow an authenticated attacker to read or modify a remote database.
3. TECHNICAL DETAILS
3.1 AFFECTED PRODUCTS
The following versions of Advantech WebAccess/SCADA, a bowser-based SCADA software, are affected:
- WebAccess/SCADA: Version 9.1.5U
3.2 Vulnerability Overview
3.2.1 IMPROPER NEUTRALIZATION OF SPECIAL ELEMENTS USED IN AN SQL COMMAND (‘SQL INJECTION’) CWE-89:
There is a SQL Injection vulnerability in Advantech’s WebAccess/SCDA software that allows an authenticated attacker to remotely inject SQL code on the database. Successful exploitation of this vulnerability could allow an attacker to read or modify data on the remote database.
CVE-2024-2453 has been assigned to this vulnerability. A CVSS v3.1 base score of 6.4 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:L/UI:N/S:C/C:L/I:L/A:N).
CVE-2024-2453 has been assigned to this vulnerability. A CVSS v4 base score of 7.1 has been calculated; the CVSS vector string is (AV:N/AC:L/AT:N/PR:L/UI:N/VC:H/VI:L/VA:N/SC:N/SI:N/SA:N).
3.3 BACKGROUND
- CRITICAL INFRASTRUCTURE SECTORS: Critical Manufacturing, Energy, Water and Wastewater Systems
- COUNTRIES/AREAS DEPLOYED: East Asia, Europe, United States
- COMPANY HEADQUARTERS LOCATION: Taiwan
3.4 RESEARCHER
CISA discovered a public Proof of Concept (PoC) as authored by Prześlij Komentarz and reported it to Advantech.
4. MITIGATIONS
Advantech recomends updating WebAccess/SCADA to version 9.1.6 or higher to mitigate this vulnerability.
CISA recommends users take defensive measures to minimize the risk of exploitation of this, such as:
- Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the internet.
- Locate control system networks and remote devices behind firewalls and isolating them from business networks.
- When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize VPN is only as secure as the connected devices.
CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.
CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov/ics. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.
CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.
Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov/ics in the technical information paper, ICS-TIP-12-146-01B–Targeted Cyber Intrusion Detection and Mitigation Strategies.
Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.
5. UPDATE HISTORY
- March 21, 2024: Initial Publication