Skip to content
mySCADA myPRO Manager | CISA

mySCADA myPRO Manager | CISA

  • by

View CSAF

1. EXECUTIVE SUMMARY

  • CVSS v4 10.0
  • ATTENTION: Exploitable remotely/low attack complexity
  • Vendor: mySCADA
  • Equipment: myPRO
  • Vulnerabilities: OS Command Injection, Improper Authentication, Missing Authentication for Critical Function, Path Traversal.

2. RISK EVALUATION

Successful exploitation of this vulnerability could allow a remote attacker to execute arbitrary commands or disclose sensitive information.

3. TECHNICAL DETAILS

3.1 AFFECTED PRODUCTS

The following mySCADA products are affected:

  • myPRO Manager: Versions prior to 1.3
  • myPRO Runtime: Versions prior to 9.2.1

3.2 Vulnerability Overview

3.2.1 Improper Neutralization of Special Elements used in an OS Command (‘OS Command Injection’) CWE-78

A parameter within a command does not properly validate input within myPRO Manager which could be exploited by an unauthenticated remote attacker to inject arbitrary operating system commands.

CVE-2024-47407 has been assigned to this vulnerability. A CVSS v3.1 base score of 10.0 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:C/C:H/I:H/A:H).

A CVSS v4 score has also been calculated for CVE-2024-47407. A base score of 10.0 has been calculated; the CVSS vector string is (CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:H/SI:H/SA:H).

3.2.2 Improper Neutralization of Special Elements used in an OS Command (‘OS Command Injection’) CWE-78

An OS Command Injection vulnerability exists within myPRO Manager. A parameter within a command can be exploited by an unauthenticated remote attacker to inject arbitrary operating system commands.

CVE-2024-52034 has been assigned to this vulnerability. A CVSS v3.1 base score of 10.0 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:C/C:H/I:H/A:H).

A CVSS v4 score has also been calculated for CVE-2024-52034. A base score of 10.0 has been calculated; the CVSS vector string is (CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:H/SI:H/SA:H).

3.2.3 Improper Authentication CWE-287

The web application uses a weak authentication mechanism to verify that a request is coming from an authenticated and authorized resource.

CVE-2024-45369 has been assigned to this vulnerability. A CVSS v3.1 base score of 8.1 has been calculated; the CVSS vector string is (AV:N/AC:H/PR:N/UI:N/S:U/C:H/I:H/A:H).

A CVSS v4 score has also been calculated for CVE-2024-45369. A base score of 9.2 has been calculated; the CVSS vector string is (CVSS:4.0/AV:N/AC:H/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N).

3.2.4 Missing Authentication for Critical Function CWE-306

The administrative interface listens by default on all interfaces on a TCP port and does not require authentication when being accessed

CVE-2024-47138 has been assigned to this vulnerability. A CVSS v3.1 base score of 9.8 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H).

A CVSS v4 score has also been calculated for CVE-2024-47138. A base score of 9.3 has been calculated; the CVSS vector string is (CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N).

3.2.5 Path Traversal: ‘…/…//’ CWE-35

The backend does not sufficiently verify the user-controlled filename parameter which makes it possible for an attacker to perform a path traversal attack and retrieve arbitrary files from the file system

CVE-2024-50054 has been assigned to this vulnerability. A CVSS v3.1 base score of 7.5 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H).

A CVSS v4 score has also been calculated for CVE-2024-50054. A base score of 8.7 has been calculated; the CVSS vector string is (CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:N/VI:N/VA:H/SC:N/SI:N/SA:N).

3.3 BACKGROUND

  • CRITICAL INFRASTRUCTURE SECTORS: Critical Manufacturing
  • COUNTRIES/AREAS DEPLOYED: Worldwide
  • COMPANY HEADQUARTERS LOCATION: Czech Republic

3.4 RESEARCHER

Michael Heinzl reported these vulnerabilities to CISA.

4. MITIGATIONS

mySCADA recommends updating to the latest versions.

  • mySCADA PRO Manager 1.3
  • mySCADA PRO Runtime 9.2.1

CISA recommends users take defensive measures to minimize the risk of exploitation of these vulnerabilities, such as:

  • Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the internet.
  • Locate control system networks and remote devices behind firewalls and isolating them from business networks.
  • When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize VPN is only as secure as the connected devices.

CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.

CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov/ics. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.

Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov/ics in the technical information paper, ICS-TIP-12-146-01B–Targeted Cyber Intrusion Detection and Mitigation Strategies.

Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.

CISA also recommends users take the following measures to protect themselves from social engineering attacks:

No known public exploitation specifically targeting these vulnerabilities has been reported to CISA at this time.

5. UPDATE HISTORY

  • November 21, 2024: Initial Publication

Source link