1. EXECUTIVE SUMMARY
- CVSS v4 9.3
- ATTENTION: Exploitable remotely/low attack complexity
- Vendor: Industrial Video & Control
- Equipment: Longwatch
- Vulnerability: IMPROPER CONTROL OF GENERATION OF CODE (‘CODE INJECTION’)
2. RISK EVALUATION
Successful exploitation of this vulnerability could allow an unauthenticated attacker to gain remote code execution with elevated privileges.
3. TECHNICAL DETAILS
3.1 AFFECTED PRODUCTS
The following versions of Industrial Video & Control Longwatch, a video surveillance and monitoring system, are affected:
- Longwatch: Versions 6.309 to 6.334
3.2 VULNERABILITY OVERVIEW
3.2.1 IMPROPER CONTROL OF GENERATION OF CODE (‘CODE INJECTION’) CWE-94
A vulnerability in Longwatch devices allows unauthenticated HTTP GET requests to execute arbitrary code via an exposed endpoint, due to the absence of code signing and execution controls. Exploitation results in SYSTEM-level privileges.
CVE-2025-13658 has been assigned to this vulnerability. A CVSS v3.1 base score of 9.8 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H).
A CVSS v4 score has also been calculated for CVE-2025-13658. A base score of 9.3 has been calculated; the CVSS vector string is (AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N).
3.3 BACKGROUND
- CRITICAL INFRASTRUCTURE SECTORS: Energy, Water and Wastewater Systems
- COUNTRIES/AREAS DEPLOYED: Worldwide
- COMPANY HEADQUARTERS LOCATION: United States
3.4 RESEARCHER
Concerned OT Engineer reported this vulnerability to CISA.
4. MITIGATIONS
Industrial Video & Control recommends users running versions 6.309 to 6.334 should upgrade to version 6.335 or later to ensure protection against this vulnerability.
For more details, view Industrial Video & Control’s advisory.
CISA recommends users take defensive measures to minimize the risk of exploitation of this vulnerability, such as:
- Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the internet.
- Locate control system networks and remote devices behind firewalls and isolating them from business networks.
- When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize VPN is only as secure as the connected devices.
CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.
CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov/ics. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.
CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.
Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov/ics in the technical information paper, ICS-TIP-12-146-01B–Targeted Cyber Intrusion Detection and Mitigation Strategies.
Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.
CISA also recommends users take the following measures to protect themselves from social engineering attacks:
No known public exploitation specifically targeting this vulnerability has been reported to CISA at this time.
5. UPDATE HISTORY
- December 2, 2025: Initial Publication